EDP70 PLUS
UNINTERRUPTIBLE POWER SYSTEM
24/36/50/80kVA –
3 phase input / 3 phase output
USER HANDBOOK
PART NUMBER 10H52152PU9C rev.1
Page view 0
1 2 3 4 5 6 ... 64 65

Summary of Contents

Page 1 - EDP70 PLUS

EDP70 PLUSUNINTERRUPTIBLE POWER SYSTEM24/36/50/80kVA –3 phase input / 3 phase outputUSER HANDBOOK PART NUMBER 10H52152PU9C rev.1

Page 2

page 10 -- MI00/10056 rev.1--05/2001Figure 5 – Re-establishing the Utility SupplyWhen the utility supply returns within acceptable limits, the UPS ret

Page 3

MI00/10056 rev.1--05/2001-- page 112.0 SAFETYRead all instructions carefully before installing or operating the equipment.2.1 General safetyThe proced

Page 4 - Contents

page 12 -- MI00/10056 rev.1--05/2001Page Right Control For explanation see Para. 6.2. of thismanualRecord Up For explanation see Para. 6.2. of thism

Page 5

MI00/10056 rev.1--05/2001-- page 133.0 STORAGEIf the EDP70 PLUS UPS cannot be installed within sixty days of delivery, there is a danger of the

Page 6 - 1.0 INTRODUCTION

page 14 -- MI00/10056 rev.1--05/2001Figure 7 – 24 Footprint and cabinet dimensionsALL MEASUREMENTS ARE INMILLIMETERS (AND INCHES)600,0 (25.39)30,0 (1.

Page 7

MI00/10056 rev.1--05/2001-- page 15Figure 8 – 36 Footprint and cabinet dimensions50,0ALL MEASUREMENTS ARE INMILLIMETERS (AND INCHES)600,0 (25.39) (1.1

Page 8 - CONNECTED AS INDICATED

page 16 -- MI00/10056 rev.1--05/2001Figure 9 – 50/80 Footprint and cabinet dimensions50,0ALL MEASUREMENTS ARE INMILLIMETERS (AND INCHES)800,0 (25.39)

Page 9 - Figure 3 – Normal operation

MI00/10056 rev.1--05/2001-- page 17Figure 10 – “A” Battery Cabinet Drawing for 24/36kVA Ratings

Page 10 - 24/36kVA Ratings

page 18 -- MI00/10056 rev.1--05/2001Figure 11 – “B” Battery Cabinet Drawing for 24/36kVA Ratings

Page 11 - ALTERNATING CURRENT SUPPLY

MI00/10056 rev.1--05/2001-- page 19Figure 12 – “E” Battery Cabinet Drawing for 50/80kVA Ratings

Page 12 - 2.5 Battery safety equipment

page 2 -- MI00/10056 rev.1--05/2001IMPORTANT SAFETY INSTRUCTIONSREAD BEFORE INSTALLING1) SAVE THESE INSTRUCTIONS This manual contains important i

Page 13 - 3.0 STORAGE

page 20 -- MI00/10056 rev.1--05/2001Figure 13 – “F” Battery Cabinet Drawing for 50/80kVA Ratings

Page 14 - MILLIMETERS (AND INCHES)

MI00/10056 rev.1--05/2001-- page 214.2 InstallationCheck the rating label on the rear of the front panel of the EDP70 PLUS UPS to ensure the input/out

Page 15

page 22 -- MI00/10056 rev.1--05/2001Recommended wire sizes1) It is recommended that the external cables and protection be selected for the highestrat

Page 16

MI00/10056 rev.1--05/2001-- page 23A.C. Supply Reserve SupplyUPS TypeVin/VoutRatedcurrent(A)Protectiondevice(A)OutputNominalcurrent(A)Nominalcurrent(A

Page 17

page 24 -- MI00/10056 rev.1--05/20014.4 VentilationUPS can work in a continuous environment within 18°F[-10°C] to 104°F [+40°C ] temperature rang

Page 18 - for 24/36kVA Ratings

MI00/10056 rev.1--05/2001-- page 255.0 CONNECTIONFigure 15 – Connection diagramsTHE AC AND DC SUPPLIES TO THE EDP70 PLUS UPS, AND THE AC OUTPUT FROM T

Page 19 - for 50/80kVA Ratings

page 26 -- MI00/10056 rev.1--05/2001UNINTERRUPTIBLE POWER SYSTEMNO UNAUTHORIZED OPERATION

Page 20

MI00/10056 rev.1--05/2001-- page 27CAUTION!WARNING!All power connection must carried out by qualified licensed personnel experiencedin wiring this typ

Page 21 - Figure 14 – UPS Ratings

page 28 -- MI00/10056 rev.1--05/20015.1 Electrical connectionsWARNING!All electrical connections mustbe made by a qualified electricianand meet local

Page 22

MI00/10056 rev.1--05/2001-- page 295.2 24 – 12/18/24kVAEnsure the AC supplies and load are switched OFF. Check that all the EDP70 PLUS UPS Switches (

Page 23

MI00/10056 rev.1--05/2001-- page 3WARNINGThe UPS contains hazardous voltages, even when all switches are open.In case of fire in the installation are

Page 24 - V = 2770 - - - - - - • e

page 30 -- MI00/10056 rev.1--05/2001Figure 17 - 24 – 12/18/24kVA: SwitchesAccess to the terminals for electrical connections is as follows:a) Remove f

Page 25 - 5.0 CONNECTION

MI00/10056 rev.1--05/2001-- page 31Figure 18 - 24 – 12/18/24kVA: Cable ConnectionsModem and Multicompower suppliesV1U1 W1N PE U V W N V2U2 NW2RESERVEI

Page 26 - NO UNAUTHORIZED OPERATION

page 32 -- MI00/10056 rev.1--05/20015.3 36 – 24/30/36kVAEnsure the AC supplies and load are switched OFF. Check that all the EDP70 PLUS UPS Switches (

Page 27 - CAUTION!

MI00/10056 rev.1--05/2001-- page 33Figure 20 - 36 – 24/30/36kVA: ConnectionsAccess to the terminals for electrical connections is as follows:a) Remove

Page 28 - WARNING!

page 34 -- MI00/10056 rev.1--05/2001Figure 21 - 36 – 24/30/36kVA: Cable ConnectionsQS4Modem and Multicompower suppliesNEUTRAL (RES/OUT)W2U1PE U V W N

Page 29 - S4 = Equipment OUTPUT Breaker

MI00/10056 rev.1--05/2001-- page 355.3 EDP70 PLUS 50/80kVAEnsure the AC supplies and load are switched OFF. Check that all the EDP70 PLUS UPS Switches

Page 30 - Cable support

page 36 -- MI00/10056 rev.1--05/2001Figure 23 – 50/80kVA: ConnectionsAccess to the terminals for electrical connections is as follows:a) Remove front

Page 31

MI00/10056 rev.1--05/2001-- page 37Figure 24 – 50/80kVA: Cable ConnectionsModem and Multicompower suppliesRAU - FEMALEComputer relayinterface - FEMALE

Page 32 - S3 = Equipment By-pass switch

page 38 -- MI00/10056 rev.1--05/20015.4 Signal connectionsa) Emergency Power OffWhen the connection between terminals 1 and 2 is opened, the UPS will

Page 33

MI00/10056 rev.1--05/2001-- page 396.0 CONTROLS6.1 User ControlsThe user controls are situated on the front panel, see Figure 25.Access to the Equip

Page 34 - W2U1PE U V W N U2V2V1W1

page 4 -- MI00/10056 rev.1--05/2001Contents1.0 INTRODUCTION...

Page 35 - 5.3 EDP70 PLUS 50/80kVA

page 40 -- MI00/10056 rev.1--05/20016.2 Control PanelInverter Start UpThis allows the user to turn on and reset the inverter. This is normally only us

Page 36

MI00/10056 rev.1--05/2001-- page 417.0 START UP1. Switch on the AC reserve and the main AC Utility supply to the UPS.2. Turn on the Utility supply Inp

Page 37 - W2 N NU2 V2 PE

page 42 -- MI00/10056 rev.1--05/20018.0 MAINTENANCE BYPASSThe EDP70 PLUS UPS is equipped with Manual Maintenance Bypass systems. If a unit requires

Page 38 - 5.4 Signal connections

MI00/10056 rev.1--05/2001-- page 43To ensure that the EPO functions correctly, the signal should remain active for a period > 400 msec.

Page 39 - 6.0 CONTROLS

page 44 -- MI00/10056 rev.1--05/200110.0 VISUAL AND AUDIBLE ALARMSThe EDP70 PLUS UPS is equipped with visual and audible alarms which indicate the s

Page 40 - 6.2 Control Panel

MI00/10056 rev.1--05/2001-- page 4510.4 Display Page HeadingsAfter initial power up, under normal operating conditions, the main page heading will be

Page 41 - 7.0 START UP

page 46 -- MI00/10056 rev.1--05/2001By pressing the button marked again, the selected battery test period appears on the display:BATTERY TESTWEEKLYTh

Page 42 - 9.0 SHUT-DOWN

MI00/10056 rev.1--05/2001-- page 47If at any time the inverter is blocked then the power history heading appears:POWER HISTORYDOWN TO ACCESSThe power

Page 43

page 48 -- MI00/10056 rev.1--05/2001RESERVE F xx.x HzAB xxx V BC xxx V CA xxx VDisplays the frequency and the phase-phase voltageof the reserve supp

Page 44 - 10.3 Liquid Crystal Display

MI00/10056 rev.1--05/2001-- page 49TIME ON RESERVExxg: xxh: xxm: xxsDisplays the total time the load has been supplied bythe reserve since the mach

Page 45 - 10.4 Display Page Headings

MI00/10056 rev.1--05/2001-- page 5FiguresFigure 1 – Block diagrams – 24/36kVA...

Page 46 - SELECTED LANGUAGE

page 50 -- MI00/10056 rev.1--05/2001The measurement signals are accessed from the battery rectifier page as follows:RECT/BATT ALARMSNO ALARMS ACTIVENo

Page 47 - DOWN TO ACCESS

MI00/10056 rev.1--05/2001-- page 51The measurement signals are accessed from the load output - reserve supply page as follows:LOAD/RES ALARMSNO ALARMS

Page 48

page 52 -- MI00/10056 rev.1--05/200110.5 Abnormal operating mode messagesUnder abnormal operating conditions, the normal functioning heading on the ma

Page 49

MI00/10056 rev.1--05/2001-- page 53a) When the battery is discharging, the machine displays the residual autonomy and the dischargingtime information.

Page 50

page 54 -- MI00/10056 rev.1--05/2001RECTIFIER/BATTERY ALARMSMESSAGE CONDITIONNOT CALIBRATEDFAULTDC FEEDBACK FAULTFAULTVERIFY DC FEEDBACKNORMALPRIMARY

Page 51 - P = 80kW s = 80kVA

MI00/10056 rev.1--05/2001-- page 55INVERTER ALARMSMESSAGE CONDITIONNOT CALIBRATEDFAULTPCB SUPPLY FAULTFAULTOUT OF SYNCWARNINGDESATURATIONFAULTOVER TEM

Page 52 - SYSTEM ALARM

page 56 -- MI00/10056 rev.1--05/2001LOAD/RESERVE ALARMSMESSAGE CONDITIONNOT CALIBRATEDFAULTLOAD ON RESERVEWARNINGLOAD NOT SUPPLIEDFAULTBYPASS SWITCH C

Page 53 - AUT calc DIS xx min

MI00/10056 rev.1--05/2001-- page 5710.6 Power HistoryThe power history is only available when the inverter is blocked; it provides a visual display of

Page 54 - MESSAGE CONDITION

page 58 -- MI00/10056 rev.1--05/200110.7 Battery TestThe EDP70 PLUS has an automatic battery control function which checks the condition of the batter

Page 55 - INVERTER ALARMS

MI00/10056 rev.1--05/2001-- page 59data has still been lost and the intervention of a qualified technician is required.It is, nevertheless, possible t

Page 56 - LOAD/RESERVE ALARMS

page 6 -- MI00/10056 rev.1--05/20011.0 INTRODUCTION1.1 Summary of the manualThis handbook provides for the safe installation, startup and use of the

Page 57 - UP TO EXIT

page 60 -- MI00/10056 rev.1--05/200111.0 COMPUTER INTERFACE11.1 AS400The EDP70 PLUS UPS is fitted with a 9 pin female ‘D’ type socket for direct con

Page 58 - 10.8 Battery Autonomy Test

MI00/10056 rev.1--05/2001-- page 6111.2 RS232The EDP70 PLUS UPS is fitted with a 9 pin male ‘D’ type plug which enables a communication link to beest

Page 59

page 62 -- MI00/10056 rev.1--05/200113.0 BATTERIES13.1 EDP70 PLUS/24/18/12 : Battery Installation/Start-upSAFETY- Ensure all the Switches are turned t

Page 60 - 11.0 COMPUTER INTERFACE

MI00/10056 rev.1--05/2001-- page 6313.2 EDP70 PLUS/24/18/12 : Optional Battery CubicleThe battery autonomy can be increased by employing either one or

Page 61 - 12.0 REMOTE ALARMS

page 64 -- MI00/10056 rev.1--05/200113.3 EDP70 PLUS above 20kVA: Battery Installation/Start-upSAFETY- Ensure the Equipment ON/OFF Switch is turned to

Page 62 - 13.0 BATTERIES

MI00/10056 rev.1--05/2001-- page 65EDP70 PLUS SYSTEM LOGIt is recommended that any maintenance action or failure of the SYSTEM be recorded in this log

Page 63

MI00/10056 rev.1--05/2001-- page 7Figure 1 – Block diagrams – 24/36kVA24kVA - STANDARD CONFIGURATIONBatteryContactor36kVA - STANDARD CONFIGURATIONBatt

Page 64

page 8 -- MI00/10056 rev.1--05/2001Figure 2 – Block diagram – 50/80kVAThe uninterruptible power system consists of the following:1 - RECTIFIER/INVERTE

Page 65 - EDP70 PLUS SYSTEM LOG

MI00/10056 rev.1--05/2001-- page 91.5 Operational modesFigure 3 – Normal operationDuring normal operation the load is supplied by the mains through th